Technichal Data Supply voltage 24V AC/DC, ±10% Power consumption max. 100 mA (terminals of supply voltage max. 2.5 A current rating) Interface RS485 (not galvanically isolated), GND combined with -/v terminal Binary Inputs: galvanically isolated Voltage Activated by +/- 24V AC/DC (positive/negative logic) Current max. 10mA per channel Analog Inputs: Sensors: Pt1000/Ni1000 and others Resistor 0..19.5 kOhm Current max. 1mA per channel Resolution 16 Bits Binary Outputs: Switching voltage max.: 250 VAC / 30 VDC Contact rating: 625 VA / 150 W Maximum switching current (resistive load): 5 A Nominal load (resistive): 2,5 A / 250 VAC; 5 A / 30 VDC Durability: at nominal load 50.000 cycles without load 5.000.000 cycles Analog Outputs: 0..10 V, max. 10mA Environmental conditions Operating temperature 0..50°C Transport and storage temperature -20..+70°C Relative humidity 5..95%, non-condensing Protection class IP20 Dimensions Width x Height x Depth: 72 x 92x 70 mm Standard installation housing, 4TE Terminals Spring-type terminal blocks, 1.0 und 1.5 m² (see page 3) Mounting DIN-rail, DIN EN50022 CE compliance CE Directive 2004/108/EG (EN50081-1, EN50082-2) CE Directive 2006/95/EG (EN60730) EN 61000-4-2 / IEC 801-2 Electrostatic discharge ESD Kontact discharge 8 kV / air discharge 8 kV EN 61000-4-5 / IEC 801-5 Surge Signal lines 2 kV EN 61000-4-4 / IEC 801-4 Burst Inputs - outputs +/- 2 kV Power supply AC / DC +/- 2 kV