Power supply 24 V AC/DC, connection via terminals Current consumption typically 68 mA (DC), 152 mA (AC), with all relays activated Power dissipation max. 1.7 W (DC), 3.7 W (AC), with all relays activated Specifications DO's: Relay outputs (NO contact), max. 250 VAC Characteristics (Resistive Load): Initial contact resistance 100mOhm (at 1A / 24 VDC) Rated load 3 A at 250 VAC / 30 VDC Max. switching voltage 277 VAC, 30 VDC Max. switching capacity 830 VA (AC), 90 W (DC) Endurance 100'000 ops (Rated Load) Inductive loads should be avoided or be suppressed at the source Counting pulse duration min. 10 ms, only for DC signals Max. counter value 4,294,967,296 counter values not stored retentively in case of power failure Bus interface RS485 Supported baud rates 9,600 Baud (Autobauding) 19,200 Baud 38,400 Baud 57,600 Baud Bus cycle time individually depending on the baud rate and the number of data points that will be addressed Memory uPC internally Configuration settings are stored in the internal EEPROM, max. number of write cycles up to 100,000 times Protocol Modbus rtu (RS485) Serial port parameter setting 8-N-1 Inputs and outputs see corresponding documentation of the respective modules Environmental conditions Operating temperature 0...50°C Transport and storage temperature 0...70°C Relative humidity 10...90%, non-condensing Protection class IP 20 Dimensions (for exact dimensions see appendix B)