The terminal designations are numbered consecutively according to the module position within an enclosure. The designation 3.6 therefore means: Internal module slot 3, terminal 6. In the following terminal list for functional unit FE02, the position is therefore marked as X. Terminal X.1: Supply voltage GND Terminal X.2: Supply voltage 24V AC or DC Terminals X.3 and X.4: Switch feedback in auto or manual position, potential-free, contact load 28V AC or DC, max. 5A, max. 100VA Terminal X.5: Relay NC contact Terminal X.6: Control of the relay with 8V to 24V AC or DC in the delivery state. Control with GND potential (AC-COM) selectable via jumper J4 Terminal X.7: Relay NO contact Terminal X.8: Relay root (COM), contact load 250V AC, 5A, max. 1250VA External dimensions: W x H x D 17.5 x 90 x 58 mm